Final | 10/17/2014 | 10/21/2014 | 10/21/2014 | P | PASS |
Rock A. Hudson
|
|
|
JR Phone #: ###-#### Final OK kitchen
|
Final | 10/13/2014 | 10/15/2014 | 10/15/2014 | P | FAIL |
Rock A. Hudson
|
|
|
JR Phone #: ###-#### 406.4(D)- All grounding type receptical outlets shall be GFCI protected that are installed on ungrounded circuits. refrigerator. 406.6- All receptical outlets and switches shall have covers. Receptical in bed room shall be tight to box and covered. Corrections not complete. Contact A-1 electric. Permit # ele14-01322 for items outside kitchen. Previous contractor no longer working on project. This permit for kitchen only. This contractor to make sure covers are install and recepticals secured to box in bed.
|
Final | 10/9/2014 | 10/10/2014 | 10/10/2014 | P | FAIL |
Bob Reichert
|
|
|
Anastacio Phone #: ###-#### called, left correction notice, NEC 406.11 all receptacles shall be tamper resistant, 110.3 receptacles shall operate per listings, BCC shall wire hood, all receptacle and switch covers shall be installed, NOTE: shall have other contractor call for final or change room count for this permit, and check all house, not just kitchen
|
Issue PAID IN FULL permit | | | 10/9/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Issue PAID IN FULL permit | | | 10/9/2014 | | DONE |
|
|
|
|
Application received | | | 10/9/2014 | | |
|
|
|
|