Final | 7/16/2015 | 7/17/2015 | 7/17/2015 | A | PASS |
Rock A. Hudson
|
|
|
Russell Phone #: ###-#### Final ok
|
Electrical Rough-In | 3/23/2015 | 3/23/2015 | 3/23/2015 | P | PASS |
Rock A. Hudson
|
|
|
Russ Phone #: ###-#### All wiring surface mounted in shop in back yard. complete conduit installed in house crawl space. In shop 314.16 handy boxes to be changed where feed through wiring is installed. 358.30(A)- EMT shall be secured with in 3' of boxes. 210.70- An outdoor lighting outlet shall be installed at man door on shop. 406.12(A)- Tamper resistant receptacle outlets shall be installed for all 15 and 20 amp 120 volt circuits. Underground and shop panel rough in ok
|
Electrical Rough-In | 11/5/2014 | 11/6/2014 | 11/6/2014 | A | PART |
Rock A. Hudson
|
|
|
Russ// please try for after 9am Phone #: 6521 Underground to shop rough in ok cover. Feeder under house not install in jacket or conduit. check on next trip
|
Issue PAID IN FULL permit | | | 10/10/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Issue PAID IN FULL permit | | | 10/10/2014 | | DONE |
Candy A. Nichols
|
|
|
|
Application received | | | 10/10/2014 | | |
|
|
|
|