First Notice | 4/20/2015 | 4/20/2015 | 11/13/2015 | | DONE |
Rex Boyles
|
|
|
|
Final | 4/17/2015 | 4/20/2015 | 4/20/2015 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Louis Keller corrections made final ok
|
Final | 4/16/2015 | 4/17/2015 | 4/17/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Final Electrical Inspection Phone #: ###-#### Inspection requested via web by Louis Keller 210.8-Bathroom receptacles in light fixtures shall have GFCI protection or be removed. 422.25-Disconnecting means shall be provided for well. Unused openings shall be closed. Shop panel. 408.4- Shop panel circuit directory shall be completed.
|
Permanent Service | 2/27/2015 | 2/27/2015 | 2/27/2015 | P | PASS |
Rock A. Hudson
|
|
|
Underground and permanent service Phone #: ###-#### Inspection requested via web by Louis Keller Underground to buildings not subject to vehicle traffic. Shop drive will be through lot to east of 11911. p/s o/h n ok
|
Electrical Rough-In | 11/24/2014 | 11/25/2014 | 11/25/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Louis Keller BBC 4-05-31(D) has been removed from electrical ordinance per Daryl DeGrange. Addition Rough in ok cover
|
Issue PAID IN FULL permit | | | 10/23/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/23/2014 | | DONE |
|
|
|
This permit was created on the web by Louis Keller
|