Final | 10/28/2014 | 10/29/2014 | 10/29/2014 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Dan Rohl final ok
|
Permanent Service | 10/27/2014 | 10/28/2014 | 10/28/2014 | A | PASS |
Daryl DeGrange
|
|
|
when calling id power please specify space #5 Phone #: ###-#### Inspection requested via web by Dan Rohl Space 5 p/s o/h rec ok
|
Final | 10/24/2014 | 10/24/2014 | 10/24/2014 | P | CANC |
Rock A. Hudson
|
|
|
SPACE # 5 Phone #: ###-#### Inspection requested via web by Dan Rohl
|
Permanent Service | 10/24/2014 | 10/24/2014 | 10/24/2014 | P | FAIL |
Rock A. Hudson
|
|
|
SPACE # 5 Phone #: ###-#### Inspection requested via web by Dan Rohl
4.05.32 Code violations not to be retained 250.53(a)(2) Supplemental electrode (ground rod) required 2 per service 314.23(A) Enclosures shall be rigidly and securly fastened in place 250.94(B) Method of Bonding at the Service. Bonding jumpers meeting the requirements of this article shall be used around impaired connections, such as reducing washers or oversized, concentric, or eccentric knockouts. Standard locknuts or bushings shall not be the only means for the bonding required by this section but shall be permitted to be installed to make a mechanical connection of the raceway(s). Electrical continuity at service equipment, service raceways, and service conductor enclosures shall be ensured by one of the following methods: (1) Bonding equipment to the grounded service conductor in a manner provided in 250.8 (2) Connections utilizing threaded couplings or threaded hubs on enclosures if made up wrenchtight (3) Threadless couplings and connectors if made up tight for metal raceways and metal-clad cables (4) Other listed devices, such as bonding-type locknuts, bushings, or bushings with bonding jumpers 230.70 Marking. Each service disconnect shall be permanently marked as to its purpose
|
Issue PAID IN FULL permit | | | 10/24/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/24/2014 | | DONE |
|
|
|
This permit was created on the web by Dan Rohl
|