First Notice | 1/7/2015 | 1/7/2015 | 1/6/2016 | | DONE |
Cevyn Recla
|
|
|
|
Print Statement | | | 9/10/2015 | | DONE |
|
|
|
|
Final | 1/6/2015 | 1/7/2015 | 1/7/2015 | A | PASS |
Cevyn Recla
|
|
|
Kevin Phone #: ###-#### corrections made, final OK
|
Final | 1/5/2015 | 1/5/2015 | 1/5/2015 | P | FAIL |
Cevyn Recla
|
|
|
Kevin Phone #: ###-#### 406.9 all outdoor receptacles shall be listed weather resistant type 110.26A1 space about electrical equipment , 3 ft. clearance in front of panels 240.4 protection of conductors, 12 awg on 30 amp 110.12 unused openings shall be closed 372.13 removal of abandoned outlets required
|
Electrical Rough-In | 11/17/2014 | 11/18/2014 | 11/18/2014 | A | PASS |
Cevyn Recla
|
|
|
Kevin Phone #: ###-#### underground conduit OK to cover
|
Electrical Rough-In | 11/10/2014 | 11/10/2014 | 11/10/2014 | P | PASS |
Cevyn Recla
|
|
|
bonding// Kevin Phone #: ###-#### Bonding ok, check for building drip cap to be bonded on Final, stub is there for it now, not connected
|
Electrical Rough-In | 11/7/2014 | 11/7/2014 | 11/7/2014 | P | FAIL |
Cevyn Recla
|
|
|
Spa bonding Phone #: ###-#### Inspection requested via web by Kevin Koomler talke to contractor 680.43D(4) all metal surfaces within 5 ft. of inside walls not seperated by permanent barrier shall be bonded
|
Issue PAID IN FULL permit | | | 11/7/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/7/2014 | | DONE |
|
|
|
This permit was created on the web by Kevin Koomler
|