Final | 3/2/2015 | 3/3/2015 | 3/3/2015 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Dan Rohl corrections made, ok final
|
Final | 1/29/2015 | 1/29/2015 | 1/29/2015 | P | FAIL |
Rock A. Hudson
|
|
|
6365 code Phone #: ###-#### Inspection requested via web by Dan Rohl 210.52(C)(1)- For counter top areas deeper than 18" from back of sink to wall receptacles shall be install for wall space. 314.20- Where boxes are installed in tile wall and are recessed 1/4" or more extension rengs shall be installed. 334.12(B)(4)- NM calbe shall not be used in a damp or wet location. In flex to AC unit. 110.3- Correct cover shall be used to cover back patio outdoor receptacle.
|
Rough-In Permanent Service | 11/12/2014 | 11/13/2014 | 11/13/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Dan Rohl Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 11/7/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/7/2014 | | DONE |
|
|
|
This permit was created on the web by Dan Rohl
|