Permit Information
Permit NumberELE14-03156
StatusFinaled
Name ULTIMATE ELECTRIC LLC
Site Address 555 W PASO FINO DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: New home wiring
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/17/20154/17/20154/17/2015APASS
DetailsDaryl DeGrange
Garage code 0500. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov correction done, final ok
Final4/16/20154/16/20154/16/2015PFAIL
DetailsRock A. Hudson
Garage code 0500. Corrections are complete. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov Missed upstairs bed closet luminaire top of stairs straight ahead. 410.16- All closet luminaires shall have enclosed lamps
Final4/10/20154/10/20154/10/2015PFAIL
DetailsRock A. Hudson
Garage code 5550. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov 110.3 receptacle outlet not working in finished portion of basement hall.
210.8- GFCI protection shall be provided for all 120 volt receptacle outlets installed in unfinished portion of basement.
410.10(D)- Luminaire installed over edge of shower shall be rated for damp location.
410.16- All closet luminaires shall have totally enclosed lamps.
314.15- Light openings on outside of house shall have blank covers rated for damp locations.
334.80- #6 NM cable for hot tub ampacity shall not exceed 55 amps. Prewire shall have GFCI protection.
408.7- Hot tub panel unused openings shall be closed.
314.23- Out light boxes shall be securely mounted.
Electrical Rough-In1/30/20151/30/20151/30/2015PPASS
DetailsCevyn Recla
floor heat
master bath floor heat ok to cover
Permanent Service1/30/20151/30/20151/30/2015PDONE
DetailsCevyn Recla
Dillion Phone #: ###-####
left message,
Perm service was done in November, checked site, not sure what inspection was wanted,
Rough-In Permanent Service11/21/201411/21/201411/21/2014PPASS
DetailsCevyn Recla
Phone #: ###-#### Inspection requested via web by daniel bibikov
corrections made. RI OK PS, UG, N, OK
Rough-In Permanent Service11/20/201411/21/201411/21/2014AFAIL
DetailsCevyn Recla
Phone #: ###-#### Inspection requested via web by daniel bibikov
still missing nail plates.

300.4A1 Nail plates required-bored holes less than 1-1/4 inch from edge of framing member
Rough-In Permanent Service11/20/201411/20/201411/20/2014PFAIL
DetailsCevyn Recla
Call daniel ###-####. The basement bath gfi splits from 12/3 home run from float switch Phone #: ###-#### Inspection requested via web by daniel bibikov
Not all corrections have been fixed.
Ground clamp is still loose, nail plates are still missing
Rough-In Permanent Service11/19/201411/19/201411/19/2014PFAIL
DetailsCevyn Recla
Phone #: ###-#### Inspection requested via web by daniel bibikov
called Daniel
210.52A2(1)outlet required within first six feet of wall space
21052A2 outlet required wall space 2 foot or greater
210.11C3 bath outlet circuit shall supply not other outlets
210.52E3 required outlets, balconies shall have at least one receptacle
210.52H. Hallway 10 foot or greater shall have at least one receptacle
300.4A1 Nail plates required-bored holes less than 1-1/4 inch from edge of framing member
110.12 Mechanical execution of work, ground clamp is loose at grounding electrode
250.70 Only one wire allowed under ground clamp
250.68A- Ground clamp to be accessible
Issue PAID IN FULL permit  11/12/2014 DONE
Payment received via Govolutions
Application received  11/12/2014 DONE
This permit was created on the web by daniel bibikov