Permit Information
Permit NumberELE14-03165
StatusFinaled
Name LYNN PROCTOR ELECTRIC
Site Address 4401 N EAGLE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Shell & Core - Install electrical service and exterior lighting.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/15/20151/15/20151/15/2015PPASS
DetailsRock A. Hudson
Please call Lynn Proctor at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor Final ok
Final1/13/20151/14/20151/14/2015AFAIL
DetailsRock A. Hudson
Please call Lynn Proctor at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor 352.30- PVC conduit shall be secured with in 3' of conduit termination.
408.4- Circuit directory shall be completed on house panel.
* Complete AC wiring
Rough-In Permanent Service1/7/20151/8/20151/8/2015APASS
DetailsRock A. Hudson
Need an inspection for a grid ceiling cover. Please call Lynn Proctor at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor Grid rough in ok cover
Rough-In Permanent Service12/4/201412/5/201412/5/2014APASS
DetailsRock A. Hudson
Please call Dan at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor Shell rough in ok cover. House service p/s u/g n ok
Electrical Rough-In12/5/201412/5/201412/5/2014PFAIL
DetailsRock A. Hudson
Please call Dan at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor
550.16-Feed to job trailer shall have seperate grouned and grounding conductors. Bonding of trailer shall not connect to a grounded conductor.
400.5-Max over current for #6 Multi conductor cable 45 amp 50 amp breaker installed. Max over current for #8 35 amp 40 amp installed.


Permanent Service11/17/201411/18/201411/18/2014APASS
DetailsRock A. Hudson
Please call Lynn Proctor at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor Will check an additional grounding electrode on future rough in due to concrete encased connection outside wall in dirt below service. p/s u/g n ok
Issue PAID IN FULL permit  11/12/2014 DONE
Payment received via Govolutions
Application received  11/12/2014 DONE
This permit was created on the web by Lynn Proctor
First Notice1/15/20151/15/2015   
DetailsRock A. Hudson