Final | 1/15/2015 | 1/15/2015 | 1/15/2015 | P | PASS |
Rock A. Hudson
|
|
|
Please call Lynn Proctor at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor Final ok
|
Final | 1/13/2015 | 1/14/2015 | 1/14/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Please call Lynn Proctor at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor 352.30- PVC conduit shall be secured with in 3' of conduit termination. 408.4- Circuit directory shall be completed on house panel. * Complete AC wiring
|
Rough-In Permanent Service | 1/7/2015 | 1/8/2015 | 1/8/2015 | A | PASS |
Rock A. Hudson
|
|
|
Need an inspection for a grid ceiling cover. Please call Lynn Proctor at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor Grid rough in ok cover
|
Rough-In Permanent Service | 12/4/2014 | 12/5/2014 | 12/5/2014 | A | PASS |
Rock A. Hudson
|
|
|
Please call Dan at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor Shell rough in ok cover. House service p/s u/g n ok
|
Electrical Rough-In | 12/5/2014 | 12/5/2014 | 12/5/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Please call Dan at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor 550.16-Feed to job trailer shall have seperate grouned and grounding conductors. Bonding of trailer shall not connect to a grounded conductor. 400.5-Max over current for #6 Multi conductor cable 45 amp 50 amp breaker installed. Max over current for #8 35 amp 40 amp installed.
|
Permanent Service | 11/17/2014 | 11/18/2014 | 11/18/2014 | A | PASS |
Rock A. Hudson
|
|
|
Please call Lynn Proctor at ###-#### if you have any questions, comments or concerns. Phone #: ###-#### Inspection requested via web by Lynn Proctor Will check an additional grounding electrode on future rough in due to concrete encased connection outside wall in dirt below service. p/s u/g n ok
|
Issue PAID IN FULL permit | | | 11/12/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/12/2014 | | DONE |
|
|
|
This permit was created on the web by Lynn Proctor
|
First Notice | 1/15/2015 | 1/15/2015 | | | |
Rock A. Hudson
|
|
|
|