Final | 2/23/2015 | 2/23/2015 | 2/23/2015 | A | PASS |
Bob Reichert
|
|
|
james is the contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson corrections made, ok final
|
Final | 2/19/2015 | 2/20/2015 | 2/20/2015 | A | FAIL |
Cevyn Recla
|
|
|
james is the contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson called James 408.4 every circuit shall be labeled clear, evident, specific purpose- unit 104 210.12 A arc fault protection required for outlets in dwelling bedrooms 314.21 non combustible materials shall be repaired so no gap greater than 1/8 inch at edge of boxes- drywall gaps around panels BCC 4.05.26 Trim out inspections require all items to be functional, outlets not working in kitchen unit 103
|
Rough-In Permanent Service | 11/25/2014 | 11/26/2014 | 11/26/2014 | A | PASS |
Rock A. Hudson
|
|
|
Please contact Tracy ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 11/18/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/18/2014 | | DONE |
|
|
|
This permit was created on the web by Tracy Robertson
|
First Notice | 2/23/2015 | 2/23/2015 | | | |
Bob Reichert
|
|
|
|