First Notice | 3/2/2015 | 3/2/2015 | 6/23/2015 | | DONE |
Rex Boyles
|
|
|
|
Final | 3/2/2015 | 3/2/2015 | 3/2/2015 | P | PASS |
Rex Boyles
|
|
|
Ron Phone #: ###-#### corrections made final ok
|
Final | 2/20/2015 | 2/20/2015 | 2/20/2015 | P | FAIL |
Cevyn Recla
|
|
|
Ron Phone #: ###-#### 250.32 Building supplied by feeder or branch circuit shall have a grounding electrode system 225.32 Seperate building, disconnecting means shall be installed at nearest point of entrance of conductors 250.104 (C) Structural Metal. Exposed structural metal that is interconnected to form a metal building frame and is not intentionally grounded or bonded and is likely to become energized shall be bonded to the service equipment enclosure;
|
Issue PAID IN FULL permit | | | 11/21/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/21/2014 | | DONE |
|
|
|
This permit was created on the web by Kevin Perez
|