Final | 2/6/2015 | 2/6/2015 | 2/6/2015 | P | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov corrections made ?Final OK
|
Final | 2/5/2015 | 2/5/2015 | 2/5/2015 | P | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 312.4 Drywall gap around box shall be no larger than 1/8 inch, unit 102 210.8.7 GFI protection required within six foot of sink unit 101 and 210 110.12 MEchanical execution of work, exhaust fan doesnt work unit 101
|
Rough-In Permanent Service | 12/8/2014 | 12/8/2014 | 12/8/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 12/8/2014 | 12/8/2014 | 12/8/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 330.30- NM cable and SER shall be supported at intervals 4 1/2' or less and secured with in 12" of boxes. Up airhandlers and ser for range 314.23- Boxes shall be securely mounted. Dryer * Complete make up and install bath fans
|
Issue PAID IN FULL permit | | | 11/21/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/21/2014 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|
First Notice | 2/6/2015 | 2/6/2015 | | | |
Cevyn Recla
|
|
|
|