Final | 12/9/2014 | 12/10/2014 | 12/10/2014 | A | PASS |
Rock A. Hudson
|
|
|
Re-inspect corrections made Call susanne for access Phone #: ###-#### Inspection requested via web by David Green Final ok
|
Final | 12/8/2014 | 12/9/2014 | 12/9/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Spoke with owner would like to meet around 9 am tues morning. suzanne ###-#### for service upgrade add panel 200.7- Conductor marked as grounded conductor used as ungrounded conductor for water heater shall be other than white or green. 300.4- holes bored less than 1 1/4" from framing surface shall have nail plates to protect NM cable from damage above panel. 422.31(B)- Water heater shall have disconnecting means. Breaker lockout acceptable. Left correction noticeand called contractor
|
Permanent Service | 12/9/2014 | 12/9/2014 | 12/9/2014 | P | PASS |
Rock A. Hudson
|
|
|
Spoke with owner would like to meet around 9 am tues morning. suzanne ###-#### for service upgrade add panel p/s u/g rec ok
|
Final | 11/25/2014 | 11/26/2014 | 11/28/2014 | P | NH |
Rock A. Hudson
|
|
|
The phone number of the electricians cell for questions is ###-####, but to gain entry, call owner Suzanne Davis ###-####. Phone #: ###-#### Inspection requested via web by David Green no answer will reschedule
|
Issue PAID IN FULL permit | | | 11/24/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/24/2014 | | DONE |
|
|
|
This permit was created on the web by David Green
|