Final | 3/14/2015 | 3/16/2015 | 3/16/2015 | A | PASS |
Daryl DeGrange
|
|
|
Please give Paul a call if you have any questions or problems.
Thank You Phone #: ###-#### Inspection requested via web by Paul Young final ok
|
Permanent Service | 1/2/2015 | 1/2/2015 | 1/2/2015 | P | PASS |
Rex Boyles
|
|
|
Please call Paul if you have any questions or problems. Thank You Phone #: ###-#### Inspection requested via web by Paul Young p/s o/h n ok
|
Electrical Rough-In | 12/23/2014 | 12/24/2014 | 12/24/2014 | A | PASS |
Rex Boyles
|
|
|
Please give Paul a call if you have any questions or problems. Thank You Phone #: ###-#### Inspection requested via web by Paul Young corrections made r/i ok
|
Electrical Rough-In | 12/23/2014 | 12/23/2014 | 12/23/2014 | P | FAIL |
Cevyn Recla
|
|
|
Please give Paul a call if any questions or problems Phone #: ###-#### Inspection requested via web by Paul Young spoke to contyractor 300.4A1 nm through bored holes shall be protected when hole is less than 1 1/4 inch from edge of framing membr 334.30 securing and supporting, cable shall be secured within 12 inches of entrance to box and supported at intervals not to exceed 4 1/2 ft. (ser at meter and above meter, switch at bottom of stairs need stack-it or some other form of securing) Rock inspected concrete encased grounding electrode while inspecting the temporary service.
|
Issue PAID IN FULL permit | | | 11/24/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/24/2014 | | DONE |
|
|
|
This permit was created on the web by Paul Young
|