Final | 12/9/2014 | 12/10/2014 | 12/10/2014 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON final ok
|
Final | 11/24/2014 | 11/25/2014 | 11/25/2014 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON(E) Cables, Raceways, or Boxes Installed in or Under Roof Decking. A cable, raceway, or box, installed in exposed or concealed locations under metal-corrugated sheet roof decking, shall be installed and supported so there is not less than 38 mm (11/2 in.) measured from the lowest surface of the roof decking to the top of the cable, raceway, or box. A cable, raceway, or box shall not be installed in concealed locations in metal-corrugated, sheet decking–type roof.
|
Issue PAID IN FULL permit | | | 11/24/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/24/2014 | | DONE |
|
|
|
This permit was created on the web by SHAWN TOMLINSON
|
First Notice | 12/10/2014 | 12/10/2014 | | | |
Rex Boyles
|
|
|
|