DOC - Permit Expired | 2/4/2019 | 2/4/2019 | 2/4/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Permanent Service | 12/1/2014 | 12/4/2014 | 12/4/2014 | P | PASS |
Rex Boyles
|
|
|
Eric will be on site Phone #: ###-#### Inspection requested via web by Eric Schroeder p/s o/h rec ok duplex with 2nd meter 3908 needed. no separate permit due to not being able to find 3908 at city but meter on site. 250.32(B)- separate nuetral conductors in sub panels. 250.53- Bond water pipe within 5 foot of entering building. Change out oversized glass fuses to correct size for old conductors.
|
Issue PAID IN FULL permit | | | 11/26/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/26/2014 | | DONE |
|
|
|
This permit was created on the web by Eric Schroeder
|