ELE-Aging Inspection | 2/8/2019 | 2/8/2019 | 2/8/2019 | | PASS |
Daryl DeGrange
|
|
|
see final
|
Final | 2/8/2019 | 2/8/2019 | 2/8/2019 | A | PASS |
Daryl DeGrange
|
|
|
corrections done, Final ok
|
Permanent Service | 12/2/2014 | 12/2/2014 | 12/2/2014 | P | FAIL |
Cevyn Recla
|
|
|
Sam Phone #: ###-#### BCC4.05.15 Work must be performed by licensed electrical contractor 250.68(A) Ground shall be accessible , no meter connection 250.53(d)2 Supplemental ground required 110.26 working space required at meter 408.41 Each grounded conductor shall terminate individually on bar 210.5(c) ungrounded conductors shall be identified 210.4(b) multiwired branch circuits shall disconnect simultaneously_ Handle ties 408.36(d) backfed device requires additional fastener 110.12A unused openings shall be closedd for protectioin, meter base and subpanel
|
Issue PAID IN FULL permit | | | 12/2/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Issue PAID IN FULL permit | | | 12/2/2014 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 12/2/2014 | | |
|
|
|
|