Final | 4/24/2015 | 4/24/2015 | 4/24/2015 | P | PASS |
Rex Boyles
|
|
|
Mark Phone #: ###-#### final ok
|
Final | 4/23/2015 | 4/23/2015 | 4/23/2015 | P | NH |
Rex Boyles
|
|
|
Mark Phone #: ###-#### no access
|
Permanent Service | 2/5/2015 | 2/5/2015 | 2/5/2015 | P | PASS |
Cevyn Recla
|
|
|
Mark Phone #: ###-#### PS, OH, N, OK
|
Rough-In Permanent Service | 2/5/2015 | 2/5/2015 | 2/5/2015 | P | CANC |
Cevyn Recla
|
|
|
Mark Phone #: ###-#### Needed PS inspection
|
Electrical Rough-In | 12/17/2014 | 12/17/2014 | 12/17/2014 | P | PASS |
Cevyn Recla
|
|
|
Mark Phone #: ###-#### corrections made, RI OK
|
Electrical Rough-In | 12/16/2014 | 12/17/2014 | 12/17/2014 | A | FAIL |
Cevyn Recla
|
|
|
Mark Phone #: ###-#### Daryl DeGrange spoke to contractor, not all corrections have been addressed.
|
Electrical Rough-In | 12/11/2014 | 12/12/2014 | 12/12/2014 | A | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Mark Hansen 210.17 Electric vehicle branch circuit shall supply no other outlets 210.52A.1 spacing, no wall space greater than 6 foot from a receptacle 210.52C.1 wall countertop space, no point greater than 24 inches from a receptacle 210.52 I dining receptacle shall be supplied from 20 amp small appliance circuit 300.13B Grounded conductor multi wire circuit, shall not depend on device 300.4 nm cable through bored hole less than 1 1/4 inch from framing member edge shall be protected The range box is rated for up to a #10 wire, you need to use a box rated for the wire installed.
|
Issue PAID IN FULL permit | | | 12/7/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/7/2014 | | DONE |
|
|
|
This permit was created on the web by Mark Hansen
|