Final | 2/19/2015 | 2/19/2015 | 2/19/2015 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made, ok final
|
Final | 2/17/2015 | 2/18/2015 | 2/18/2015 | A | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn called Darryn 110.3.B listed or labeled equipment shall be installed in accordance with instructions, lockouts all fell off with panel cover 110.12 A Unused openings shall be closed, panel 210.5 Ungrounded conductors shall be permanently identified 422.11 e overcurrent protection shall not exceed that marked on appliance 408.4 Every circuit shall be legibly identified to its purpose, and accurately identified.
|
Rough-In Permanent Service | 12/9/2014 | 12/9/2014 | 12/9/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn ri ok, p/s u/g n ok
|
Issue PAID IN FULL permit | | | 12/9/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/9/2014 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|