First Notice | 12/11/2014 | 12/11/2014 | 12/22/2014 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Kerri Hamilton
|
Temporary Service | 12/10/2014 | 12/11/2014 | 12/11/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton corrections made, t/s u/g n ok
|
Temporary Service | 12/9/2014 | 12/10/2014 | 12/10/2014 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton met electrician, left correction notice, NEC 590.6(B)(1) shall provide gfci protection for cable, 400.5(A) minimum size #4 type so for 60A service, 400.10 shall supply strain relief, 1120.12(A) close unused openings at trailer, 408.4 label circuits, 230.42 shall provide 60A service to trailer, 352.10(F) exposed pvc shall be schedule 80
|
Issue PAID IN FULL permit | | | 12/9/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/9/2014 | | DONE |
|
|
|
This permit was created on the web by Kerri Hamilton
|