Permit Information
Permit NumberELE14-03420
StatusFinaled
Name TRADITIONAL ELECTRIC
Site Address 2590 N HEAVENS WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: new home
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/31/20153/31/20153/31/2015PPASS
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Emmet Bushman Inground Hot Tub permited by other contractor, correction done, final ok
Final3/31/20153/31/20153/31/2015ACANC
DetailsBob Reichert
see 3/30 pm response
Final3/30/20153/30/20153/31/2015PFAIL
DetailsBob Reichert
Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman called to pot hole post light for u/g, repair up patio receptacle, mbr receptacle cover, move bush from front of meter, contractor will call for name of contractor for hot tub
Electrical Rough-In12/16/201412/17/201412/17/2014APASS
DetailsRock A. Hudson
fire caulking will be complete in the a.m. Phone #: ###-#### Inspection requested via web by Emmet Bushman Rough in ok cover
Permanent Service12/17/201412/17/201412/17/2014PPASS
DetailsRock A. Hudson
fire caulking will be complete in the a.m. Phone #: ###-#### Inspection requested via web by Emmet Bushman p/s u/g n ok
Rough-In Permanent Service12/15/201412/16/201412/16/2014PFAIL
DetailsCevyn Recla
reinspect service clearances, recess cans outside, crawl access, kitchen island wiring Phone #: ###-#### Inspection requested via web by Emmet Bushman
WUI zone fire area, recessed can boxes must be fire caulked at openings
Rough-In Permanent Service12/11/201412/12/201412/12/2014AFAIL
DetailsCevyn Recla
Phone #: ###-#### Inspection requested via web by Emmet Bushman
spoke to Emmett
WUI zone, cans in soffit need building approval before cover,
110.26 A working clearance, meter base needs 3 feet
210.52C1 kitchen wall countertop space, no more than 24 inches to receptacles
320.23 NM cable shall be protected at attic access within 6 feet of opening
300.4 bored holes- protect nm cable through bored holes with less than 1 1/4 inch to framing member edge.
Issue PAID IN FULL permit  12/11/2014 DONE
Payment received via Govolutions
Application received  12/11/2014 DONE
This permit was created on the web by Emmet Bushman