Final | 2/11/2015 | 2/11/2015 | 2/11/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
Final | 2/10/2015 | 2/10/2015 | 2/10/2015 | P | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov called 110.3 B Listed or labeled equipment shall be installed in accordance to instructions. All breaker lockouts fell offf wtih panel cover removal 408.4 Every circuit shall be legibly identified, house panel schedule 210.5C Ungrounded conductors shall be identified, panels of all units 314.20 In walls of combustible material, boxes or extensions shall be flush with finished surfaces, microwave boxes BCC 4.05.26 Trim out inspections, all plates shall be installed
|
Rough-In Permanent Service | 12/17/2014 | 12/18/2014 | 12/18/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 12/16/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/16/2014 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|
First Notice | 2/11/2015 | 2/11/2015 | | | |
Rock A. Hudson
|
|
|
|