Final | 2/17/2015 | 2/17/2015 | 2/17/2015 | P | PASS |
Cevyn Recla
|
|
|
Garage code 0500 Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov corrections made, Final OK
|
Final | 2/13/2015 | 2/13/2015 | 2/13/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Garage code 0500 Phone #: ###-#### Inspection requested via web by daniel bibikov 110.12(B)- Installation not complete. Kitchen outlets not working. 314.25- All boxes shall have covers. Switch under stairs.
|
Rough-In Permanent Service | 12/19/2014 | 12/19/2014 | 12/19/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 12/17/2014 | 12/18/2014 | 12/18/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 300.4(B)- Listed bushings shall be installed in holes in metal side of furnace. 334.30- NM cable shall be secured within 12" of boxes. 320.23- Cables shall be protected with in 7' of attic access. 314.17- NM cable sheathing shall enter box knock out a minimum of 1/4". Temporary receptical outlets need installed. Can't approve a service with stripped wires hanging out of boxes.
|
Issue PAID IN FULL permit | | | 12/16/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/16/2014 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|