Temporary Service | 12/18/2014 | 12/18/2014 | 12/18/2014 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL t/s u/g n ok
|
Temporary Service | 12/16/2014 | 12/17/2014 | 12/17/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL 110.12(A)- Unused openings shall be closed. 110.27- Live parts shall be guarded against accidental contact. Secure panel cover. 590.6(B)- Recepticals other than 120 volt shall have GFCI protection
|
Issue PAID IN FULL permit | | | 12/16/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/16/2014 | | DONE |
|
|
|
This permit was created on the web by JENNY EMEL
|
First Notice | 12/18/2014 | 12/18/2014 | | | |
Rock A. Hudson
|
|
|
|