Final | 2/19/2015 | 2/19/2015 | 2/19/2015 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made, ok final
|
Final | 2/18/2015 | 2/18/2015 | 2/18/2015 | A | NR |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn BCC 4.5.26 Trim out inspection, all items need to be working and installed.
|
Rough-In Permanent Service | 12/17/2014 | 12/17/2014 | 12/17/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn ri ok, p/s u/g n ok
|
Issue PAID IN FULL permit | | | 12/17/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/17/2014 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|