Final | 5/6/2015 | 5/6/2015 | 5/6/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald Final ok
|
Rough-In Permanent Service | 1/6/2015 | 1/7/2015 | 1/7/2015 | A | PASS |
Rock A. Hudson
|
|
|
Please Contact Ben if any questions. Phone #: ###-#### Inspection requested via web by Ben Archibald Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 1/6/2015 | 1/6/2015 | 1/6/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Contact Ben if any questions Phone #: ###-#### Inspection requested via web by Ben Archibald 210.52(G)(1)- Each garage space shall have a receptacle outlet installed for that space that shall be fed by a dedicated circuit that shall feed no other outlets. 300.4- Where bored holes are less than 1 1/4" from framing surface NM cable shall be protected from physical damage. 300.4(D)- NM cable shall not be secured less than 1 1/4" from framing surface. Stapling side by side on 2x4 studs. 334.40(A)- NM cable shall terminated in a box. entry christmas. 590.6(B)- Receptacle temporary outlets other than 120 volt shall have GFCI protection
|
Issue PAID IN FULL permit | | | 1/5/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/5/2015 | | DONE |
|
|
|
This permit was created on the web by Ben Archibald
|