Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE15-00086
StatusFinaled
Name STEPHENS ELECTRIC INC
Site Address 5402 W SITES DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/2/20152/2/20152/2/2015PPASS
DetailsRex Boyles
The Access code is 5373, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren final ok
Permanent Service2/2/20152/2/20152/2/2015PPASS
DetailsRex Boyles
The Access code is 5373, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren corrections made p/s o/h rec ok
Permanent Service1/13/20151/14/20151/14/2015AFAIL
DetailsRex Boyles
There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering. Phone #: ###-#### Inspection requested via web by Stephen Kren 250.52(A)(5)-verify ground rod and supplemental as per 250.53(2). 250.52(1) grounding conductor to underground water pipe and water heater cold and hot jumper.
Issue PAID IN FULL permit  1/13/2015 DONE
Payment received via Govolutions
Application received  1/13/2015 DONE
This permit was created on the web by Stephen Kren