Permit Information
Permit NumberELE15-00126
StatusFinaled
Name SPENCER ELECTRIC
Site Address 9509 W WOODLAND DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: new const
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/30/20153/31/20153/31/2015APASS
DetailsRock A. Hudson
Ron Phone #: ###-#### Final ok
Final3/26/20153/26/20153/26/2015PFAIL
DetailsRock A. Hudson
code 5151enter Phone #: ###-#### Inspection requested via web by ron spen cer 210.12- All 15 and 20 amp 120 volt outlets shall have AFCI protection. Master and smokes.
408.4- Master bed miss labeled.
110.3 Washer receptacle reverse polarity.
210.8- All 120 volt recetacles located with in 6' of sink shall have GFCI protection. Back sid of kit sink.
Permanent Service1/21/20151/21/20151/21/2015PPASS
DetailsRock A. Hudson
ron ###-#### p/s u/g n ok
Permanent Service1/20/20151/20/20151/20/2015PFAIL
DetailsRock A. Hudson
310.15(B)(7)- In no case shall the service entrance conductors be sized less than 83% of the service rating. 125 amp x 83%= 103.75 amps. Table 310.15(B)(16)- 75* #2 minimum size required.
Electrical Rough-In1/20/20151/20/20151/20/2015PPASS
DetailsRock A. Hudson
Rough in ok cover
Rough-In Permanent Service1/20/20151/20/20151/20/2015PCANC
DetailsRock A. Hudson
See rough in
Issue PAID IN FULL permit  1/19/2015 DONE
Payment received via Govolutions
Application received  1/19/2015 DONE