Final | 10/12/2015 | 10/13/2015 | 10/13/2015 | A | PASS |
Rock A. Hudson
|
|
|
garage code 0813 Phone #: ###-#### Inspection requested via web by cal crosby Final ok
|
Final | 10/8/2015 | 10/8/2015 | 10/8/2015 | P | FAIL |
Rock A. Hudson
|
|
|
garage code 0813 Phone #: ###-#### Inspection requested via web by cal crosby 314.21- Garage drywall shall be repaired around boxes so no gap around box exceeds 1/8". *Mis-wire in kitchen and dining boxes. 3-way for kitchen lights locks out power to dining light. 440.6(A)- Max overcurrent device 25 amp on nameplate 30 amp installed.
|
Rough-In Permanent Service | 3/22/2015 | 3/23/2015 | 3/23/2015 | P | PASS |
Rex Boyles
|
|
|
Cal Phone #: ###-#### Inspection requested via web by cal crosby r/i ok p/s o/h rec ok
|
Conference | 1/23/2015 | 1/23/2015 | 1/23/2015 | P | DONE |
Cevyn Recla
|
|
|
Please call for a time that works for you. I will be in Meridian and can leave at any time. Thank you, Cal Phone #: ###-#### Inspection requested via web by cal crosby Meter base has to be moved, discussion of allowing conduit run on exterior of building, and connecting to existing entrance to conduit feed to basement main breaker panel. Home will keep existiing run of approsximately 18-24 inches of unfused conductor inside home to panel from meter.
|
Issue PAID IN FULL permit | | | 1/23/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/23/2015 | | DONE |
|
|
|
This permit was created on the web by cal crosby
|