Final | 2/5/2015 | 2/6/2015 | 2/6/2015 | A | PASS |
Rock A. Hudson
|
|
|
garage door code: 3655 front door code: 25579 Phone #: ###-#### Inspection requested via web by Richard Gratiot Final ok
|
Final | 2/3/2015 | 2/4/2015 | 2/4/2015 | A | FAIL |
Rock A. Hudson
|
|
|
front door code 23579 or garage door code 3655 Thanks!! Phone #: ###-#### Inspection requested via web by Richard Gratiot 110.7- Wiring shall be complete. Open ground in dining room. Open neutral in basement bed. 210.8- All garage receptacle outlets located in garage shall have GFCI protection. 300.15- Dishwasher wire shall terminate in a box. 314.16- Box located in basement storage room overfilled. Has 7 12-2 MN cables terminated in it. 314.20- Receptacle outlets located in basement on wood panelling shall be flush or have spark rings installed. 334.30- MN cable located in basement storage room shall be secured within `12" of boxes and every 4 1/2'. 408.4- Complete panel directory. ELE14-02029 open on property for service reconnect. Most recent contractor said he would complete panel derectory
|
Issue PAID IN FULL permit | | | 2/3/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/3/2015 | | DONE |
|
|
|
This permit was created on the web by Richard Gratiot
|