Final | 4/17/2015 | 4/17/2015 | 4/17/2015 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder ok final
|
Permanent Service | 2/9/2015 | 2/9/2015 | 2/9/2015 | P | PASS |
Rex Boyles
|
|
|
Code #MJS Phone #: ###-#### Inspection requested via web by Eric Schroeder p/s u/g rec ok will look for supplemental ufer and water bond upon return.
|
Permanent Service | 2/6/2015 | 2/9/2015 | 2/9/2015 | A | FAIL |
Rex Boyles
|
|
|
Lock box #MJS, call Eric with any questions. Phone #: ###-#### Inspection requested via web by Eric Schroeder 250.53(2)-supplemental grounding electrode required. 250.104(A)-a metal water piping system shall be bonded to the service equiptment.
|
Issue PAID IN FULL permit | | | 2/6/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/6/2015 | | DONE |
|
|
|
This permit was created on the web by Eric Schroeder
|