VOIDED CHANGE STATUS | | | 6/22/2016 | | DONE |
|
|
|
Per Mandy building owner told them he was going to do the work himself. Informed her that he can't cause it's a commercial building. Gave her Erics number and she is going to tell him what's going on
|
Electrical Rough-In | 2/5/2016 | 2/5/2016 | 2/5/2016 | P | PASS |
Rock A. Hudson
|
|
|
REQUEST FOR UNDERGROUND INSPECTION ON WEST SIDE. Phone #: ###-#### Inspection requested via web by Daniel Schaffeld Underground wist side 1 ft off fence to back corner of lot. Rough in ok cover
|
Electrical Rough-In | 10/28/2015 | 10/29/2015 | 10/29/2015 | A | PASS |
Rock A. Hudson
|
|
|
Butch Phone #: ###-#### Walls and hardlids all units rough in ok cover
|
Electrical Rough-In | 10/28/2015 | 10/28/2015 | 10/28/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Butch Phone #: ###-#### 210.63- A 120 volt 15 or 20 amp receptacle outlet shall be located with in 25' of HVAC units outside east and west. 210.64- A 120 volt 15 or 20 amp receptacle outlet shall be located with in 50' of electrical service equipment. 300.15- MC cable shall terminate in a box by middle door. 314.22- Surface extension or mudring shall be installed on box west wall switch. HVAC-AC disconnecting means shall be located at least 2' measured horizonally from gas meter vent.
|
Electrical Rough-In | 10/14/2015 | 10/16/2015 | 10/16/2015 | A | PASS |
Rock A. Hudson
|
|
|
ROUGH-IN INSPECTION ON THE NORTH END OF BLDG Phone #: ###-#### Inspection requested via web by Daniel Schaffeld Walls in north unit only rough in ok cover
|
Permanent Service | 10/16/2015 | 10/16/2015 | 10/16/2015 | P | PASS |
Rock A. Hudson
|
|
|
ROUGH-IN INSPECTION ON THE NORTH END OF BLDG Phone #: ###-#### Inspection requested via web by Daniel Schaffeld House panel. p/s u/g n ok
|
Electrical Rough-In | 10/13/2015 | 10/14/2015 | 10/14/2015 | A | CANC |
Rock A. Hudson
|
|
|
Butch Phone #: ###-#### Requested for wrong day, should have been Friday.
|
Rough-In Permanent Service | 10/6/2015 | 10/7/2015 | 10/7/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Daniel Schaffeld Main breakers not on sight. 110.24- Available fault current shall be posted and shall have dated calculated prior to permanent service approval.
|
Electrical Rough-In | 3/2/2015 | 3/3/2015 | 3/3/2015 | A | PASS |
Bob Reichert
|
|
|
Additional underground - 2" conduits, East side Phone #: ###-#### Inspection requested via web by Daniel Schaffeld ok cover 2 conduits east side building
|
Electrical Rough-In | 2/16/2015 | 2/17/2015 | 2/17/2015 | P | PASS |
Cevyn Recla
|
|
|
Uffer-ground inspection - East side Phone #: ###-#### Inspection requested via web by Daniel Schaffeld approx 25 ft. #4 awg in footing, OK to cover
|
Electrical Rough-In | 2/13/2015 | 2/13/2015 | 2/13/2015 | P | PASS |
Rex Boyles
|
|
|
Underground from East to North Phone #: ###-#### Inspection requested via web by Daniel Schaffeld u.ground east to north r/i ok
|
Electrical Rough-In | 2/9/2015 | 2/9/2015 | 2/9/2015 | P | PASS |
Rock A. Hudson
|
|
|
Underground inspection needed. Please contact Butch with any questions. Phone #: ###-#### Inspection requested via web by Daniel Schaffeld 1 1/2" and 2" down east side of lot rough in ok cover
|
Issue PAID IN FULL permit | | | 2/9/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/9/2015 | | DONE |
|
|
|
This permit was created on the web by Daniel Schaffeld
|