Permit Information
Permit NumberELE15-00338
StatusVoid/No Violation
Name SCHAFFELD ELECTRICAL SERVICES
Site Address 7881 W MOSSY CUP ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: Install all electrical for new building
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
VOIDED CHANGE STATUS  6/22/2016 DONE
Per Mandy building owner told them he was going to do the work himself. Informed her that he can't cause it's a commercial building. Gave her Erics number and she is going to tell him what's going on
Electrical Rough-In2/5/20162/5/20162/5/2016PPASS
DetailsRock A. Hudson
REQUEST FOR UNDERGROUND INSPECTION ON WEST SIDE. Phone #: ###-#### Inspection requested via web by Daniel Schaffeld
Underground wist side 1 ft off fence to back corner of lot. Rough in ok cover
Electrical Rough-In10/28/201510/29/201510/29/2015APASS
DetailsRock A. Hudson
Butch Phone #: ###-####
Walls and hardlids all units rough in ok cover
Electrical Rough-In10/28/201510/28/201510/28/2015PFAIL
DetailsRock A. Hudson
Butch Phone #: ###-####
210.63- A 120 volt 15 or 20 amp receptacle outlet shall be located with in 25' of HVAC units outside east and west.
210.64- A 120 volt 15 or 20 amp receptacle outlet shall be located with in 50' of electrical service equipment.
300.15- MC cable shall terminate in a box by middle door.
314.22- Surface extension or mudring shall be installed on box west wall switch.
HVAC-AC disconnecting means shall be located at least 2' measured horizonally from gas meter vent.
Electrical Rough-In10/14/201510/16/201510/16/2015APASS
DetailsRock A. Hudson
ROUGH-IN INSPECTION ON THE NORTH END OF BLDG Phone #: ###-#### Inspection requested via web by Daniel Schaffeld Walls in north unit only rough in ok cover
Permanent Service10/16/201510/16/201510/16/2015PPASS
DetailsRock A. Hudson
ROUGH-IN INSPECTION ON THE NORTH END OF BLDG Phone #: ###-#### Inspection requested via web by Daniel Schaffeld House panel. p/s u/g n ok
Electrical Rough-In10/13/201510/14/201510/14/2015ACANC
DetailsRock A. Hudson
Butch Phone #: ###-#### Requested for wrong day, should have been Friday.
Rough-In Permanent Service10/6/201510/7/201510/7/2015AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Daniel Schaffeld Main breakers not on sight.
110.24- Available fault current shall be posted and shall have dated calculated prior to permanent service approval.
Electrical Rough-In3/2/20153/3/20153/3/2015APASS
DetailsBob Reichert
Additional underground - 2" conduits, East side Phone #: ###-#### Inspection requested via web by Daniel Schaffeld ok cover 2 conduits east side building
Electrical Rough-In2/16/20152/17/20152/17/2015PPASS
DetailsCevyn Recla
Uffer-ground inspection - East side Phone #: ###-#### Inspection requested via web by Daniel Schaffeld
approx 25 ft. #4 awg in footing, OK to cover
Electrical Rough-In2/13/20152/13/20152/13/2015PPASS
DetailsRex Boyles
Underground from East to North Phone #: ###-#### Inspection requested via web by Daniel Schaffeld u.ground east to north r/i ok
Electrical Rough-In2/9/20152/9/20152/9/2015PPASS
DetailsRock A. Hudson
Underground inspection needed. Please contact Butch with any questions. Phone #: ###-#### Inspection requested via web by Daniel Schaffeld 1 1/2" and 2" down east side of lot rough in ok cover
Issue PAID IN FULL permit  2/9/2015 DONE
Payment received via Govolutions
Application received  2/9/2015 DONE
This permit was created on the web by Daniel Schaffeld