Final | 6/9/2015 | 6/9/2015 | 6/9/2015 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender ok final
|
Electrical Rough-In | 2/27/2015 | 3/2/2015 | 3/2/2015 | A | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Discusssed with contractor j box to right of tub in in attic space at floor level needing access prior to inspection. Verify access to this j box at final. picture on phone. RI ok to cover
|
Electrical Rough-In | 2/26/2015 | 2/26/2015 | 2/26/2015 | A | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Called Mike 250.148 (C) Metal Boxes. A connection shall be made between the one or more equipment grounding conductors and a metal box by means of a grounding screw that shall be used for no other purpose, equipment listed for grounding, or a listed grounding device. 300.4(A) Cables and Raceways Through Wood Members. (1) Bored Holes. In both exposed and concealed locations, where a cable- or raceway-type wiring method is installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than 32 mm (11/4 in.) from the nearest edge of the wood member. Where this distance cannot be maintained, the cable or raceway shall be protected from penetration by screws or nails by a steel plate(s) or bushing(s), at least 1.6 mm (1/16 in.) thick, and of appropriate length and width installed to cover the area of the wiring. 314.29 Boxes, Conduit Bodies, and Handhole Enclosures to Be Accessible. Boxes, conduit bodies, and handhole enclosures shall be installed so that the wiring contained in them can be rendered accessible without removing any part of the building or structure or, in underground circuits, without excavating sidewalks, paving, earth, or other substance that is to be used to establish the finished grade.
|
Electrical Rough-In | 2/16/2015 | 2/17/2015 | 2/17/2015 | A | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender RI Floor cover OK thrid floor
|
Issue PAID IN FULL permit | | | 2/9/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/9/2015 | | DONE |
|
|
|
This permit was created on the web by kendall bender
|