Final | 2/13/2015 | 2/18/2015 | 2/18/2015 | A | PASS |
Rock A. Hudson
|
|
|
Shannon is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Final ok
|
Final | 2/11/2015 | 2/12/2015 | 2/12/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Please call Shannon 30 min prior at ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Furnace located in crawl, access in back yard. Verbal with wireman. 210.63- Heating, Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, airconditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 7.5 m (25 ft) of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. 210.70 Lighting Outlets Required. Lighting outlets shall be installed where specified in 210.70(A), (B), and (C). (3) Storage or Equipment Spaces. For attics, underfloor spaces, utility rooms, and basements, at least one lighting outlet containing a switch or controlled by a wall switch shall be installed where these spaces are used for storage or contain equipment requiring servicing. At least one point of control shall be at the usual point of entry to these spaces. The lighting outlet shall be provided at or near the equipment requiring servicing.
|
Issue PAID IN FULL permit | | | 2/11/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/11/2015 | | DONE |
|
|
|
This permit was created on the web by Shawna Gates
|