DOC - Permit Expired | 2/4/2019 | 2/4/2019 | 2/4/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Electrical Rough-In | 4/6/2015 | 4/7/2015 | 4/7/2015 | P | PASS |
Daryl DeGrange
|
|
|
Mark Phone #: ###-#### correction done, rough-in ok cover master bathroom
|
Electrical Rough-In | 4/2/2015 | 4/3/2015 | 4/3/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Mark Phone #: ###-#### turned into conference. Shall provide adequate box fill, shall maintain 12-2 MN cable on 20 amp circuit, shall change breaker feeding bathroom receptacles to 20 amp, shall secure NM cables with in 12" of boxes, shall install AFCI protection for bedroom receptacles added, shall install tamper resistant receptacles.
|
Application received | | | 2/11/2015 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 2/11/2015 | | DONE |
|
|
|
|