Final | 5/14/2015 | 5/14/2015 | 5/14/2015 | P | PASS |
Rock A. Hudson
|
|
|
Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
|
Final | 5/12/2015 | 5/13/2015 | 5/13/2015 | A | FAIL |
Rock A. Hudson
|
|
|
If you have any questions, please call the office. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 210.52(A)(2)(1)- Receptacle outlet shall be installed family room 2' wall space to left of fireplace. Receptacles located in cabinets do not qualify. 210.52(C)(1)- Receptacle outlet shall be installed to serve counter top by refrigerator with in 24" of edge and with in 4' of next receptacle. 210.51(D)- In main bath upstairs a receptacle outlet shall be installed for each basin and shall be ajacent to each basin. 422.30- Lock out provided for hood lock out shall be complete. Handle loop.
|
Rough-In Permanent Service | 2/27/2015 | 3/2/2015 | 3/2/2015 | A | PASS |
Cevyn Recla
|
|
|
If you have any questions, please call Clay. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan RI interior OK to cover, need firecaulk on exterior boxes prior to soffit cover. P/S, U/G, N, OK
|
Issue PAID IN FULL permit | | | 2/13/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/13/2015 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|