Final | 2/13/2015 | 2/17/2015 | 2/17/2015 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by cal crosby changed to t/s
|
Temporary Service | 2/17/2015 | 2/17/2015 | 2/17/2015 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by cal t/s u/g n ok
|
Issue PAID IN FULL permit | | | 2/13/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/13/2015 | | DONE |
|
|
|
This permit was created on the web by cal crosby
|