DOC - Permit Expired | 2/4/2019 | 2/4/2019 | 2/4/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Permanent Service | 2/20/2015 | 2/23/2015 | 2/23/2015 | P | PASS |
Rock A. Hudson
|
|
|
Call for garage code. ###-#### Phone #: ###-#### Inspection requested via web by Rowdy Monroe Will final when wiring for AC disconnect is terminated in a box or AC unit. Confirmed disconnect is in the off position. p/s o/h rec ok
|
Permanent Service | 2/19/2015 | 2/20/2015 | 2/20/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Call ###-#### for Door Code Phone #: ###-#### Inspection requested via web by Rowdy Monroe 110.12(B)- Integrity of Electrical Equipment and Connections. Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues. There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment. Several strands broke on grounding electrode conductor. Corrosion of ground rod.
|
Issue PAID IN FULL permit | | | 2/19/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/19/2015 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|