First Notice | 8/6/2015 | 8/6/2015 | 3/22/2016 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Barbara Szurgot
|
Permanent Service | 10/16/2015 | 10/16/2015 | 10/16/2015 | P | PASS |
Rock A. Hudson
|
|
|
p/s u/g n ok
|
(F) Reprint permit | | | 10/13/2015 | | DONE |
|
|
|
|
Final | 8/5/2015 | 8/6/2015 | 8/6/2015 | A | PASS |
Rock A. Hudson
|
|
|
Please call Doug if you have any questions. ###-#### Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
|
Permanent Service | 6/3/2015 | 6/3/2015 | 6/3/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.12(A)- unused openings shall be closed. Close main opening not used. 110.24(A)- Service equipment shall be legibly marked in the field with max available fault current. Marking shall include date calculated and be durable to with stand environment. 250.24- Grounding electrode conductor shall be connected to grounded conductor. Unable to verify connection.
|
Electrical Rough-In | 3/24/2015 | 3/25/2015 | 3/25/2015 | P | PASS |
Rock A. Hudson
|
|
|
Ceiling inspection Phone #: ###-#### Inspection requested via web by Barbara Szurgot Grid rough in ok cover
|
Electrical Rough-In | 2/26/2015 | 2/27/2015 | 2/27/2015 | A | PASS |
Rock A. Hudson
|
|
|
wall inspection Phone #: ###-#### Inspection requested via web by Barbara Szurgot Perimeter walls and wall and hard lids for baths and broom closet rough in ok cover
|
Issue PAID IN FULL permit | | | 2/24/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/24/2015 | | DONE |
|
|
|
This permit was created on the web by Barbara Szurgot
|