Final | 3/5/2015 | 3/6/2015 | 3/6/2015 | A | PASS |
Cevyn Recla
|
|
|
General will be in on site from 9-10am Phone #: ###-#### Inspection requested via web by Kotton Corder corrections made, final oK
|
Final | 3/4/2015 | 3/5/2015 | 3/5/2015 | A | NH |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Kotton Corder No access, nobody home
|
Final | 2/24/2015 | 2/25/2015 | 2/25/2015 | P | FAIL |
Cevyn Recla
|
|
|
Wood spa on upper deck. Phone #: ###-#### Inspection requested via web by Kotton Corder 680.22 (3) Other Receptacles, Location. Other receptacles shall be not less than 1.83 m (6 ft) from the inside walls of a pool. 680.22. B (3) Existing Installations. Existing luminaires and lighting outlets located less than 1.5 m (5 ft) measured horizontally from the inside walls of a pool shall be not less than 1.5 m (5 ft) above the surface of the maximum water level, shall be rigidly attached to the existing structure, and shall be protected by a ground-fault circuit interrupter. 680.26 (7) Fixed Metal Parts. All fixed metal parts shall be bonded including, but not limited to, metal-sheathed cables and raceways, metal piping, metal awnings, metal fences, and metal door and window frames 680.26(C) Pool Water. Where none of the bonded parts is in direct connection with the pool water, the pool water shall be in direct contact with an approved corrosion-resistant conductive surface that exposes not less than 5800 mm2 (9 in.2) of surface area to the pool water at all times. The conductive surface shall be located where it is not exposed to physical damage or dislodgement during usual pool activities, and it shall be bonded in accordance with 680.26(B)
|
Issue PAID IN FULL permit | | | 2/24/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/24/2015 | | DONE |
|
|
|
This permit was created on the web by Kotton Corder
|