Final | 4/17/2015 | 4/17/2015 | 4/17/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
|
Final | 4/16/2015 | 4/17/2015 | 4/17/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Key in front outlet for entry Phone #: ###-#### Inspection requested via web by TOM BICANDI 210.8- All 120 volt receptacle outlets located within 6' of sink shall have GFCI protection. Back side of kitchen sink. 314.20- Boxes with non-combustable surface shall not be recessed more than 1/4" with out box extender. boxes in tile. Wire AC unit
|
Rough-In Permanent Service | 3/4/2015 | 3/5/2015 | 3/5/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 3/4/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/4/2015 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|