Final | 8/31/2015 | 9/1/2015 | 9/1/2015 | A | PASS |
Rock A. Hudson
|
|
|
Lockbox is on the front light, code is 3975. If you have any questions please call Clay at ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
|
Final | 8/28/2015 | 8/28/2015 | 8/28/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Lockbox is on the front light, code is 3975, if you have any questions, please call Clay ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 210.8(A)(7)- All receptacle outlets located with in 6' of a sink shall have GFCI protection. 422.33- Cord and plug connected appliances shall have a accessible disconnect. 110.25- Lock out acceptable. Microwave. 430.102(A)- Motors shall have a disconnecting means. 110.25 Lock out acceptable. Well
|
Electrical Rough-In | 3/16/2015 | 3/16/2015 | 3/16/2015 | P | PASS |
Rock A. Hudson
|
|
|
Lock box is 3975. Give me a call if you have any questions. Thanks Phone #: ###-#### Inspection requested via web by Clay Morgan Up kitchen, family rm stair wall, sky lights, all bathrooms, master bed and bath, down wet bar, rec rm fireplace rough in ok cover
|
Issue PAID IN FULL permit | | | 3/6/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/6/2015 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|