First Notice | 5/12/2015 | 5/12/2015 | 6/5/2015 | | DONE |
Rex Boyles
|
|
|
This permit finaled on the web by John Edwards
|
Final | 5/12/2015 | 5/12/2015 | 5/12/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by John Edwards final ok corrections made
|
Final | 5/11/2015 | 5/11/2015 | 5/11/2015 | P | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by John Edwards 210.8(B)(2)- all 15 and 20amp 120volt recetacles in kitchens (other than dwellings) shall have GFCI protection. 110.16- arc flash warning label on loadcenter required.
|
Electrical Rough-In | 4/23/2015 | 4/23/2015 | 4/23/2015 | A | PASS |
Rex Boyles
|
|
|
please call 1 hour prior. would like late morning time if possible. Phone #: ###-#### Inspection requested via web by John Edwards r/i ok to cover walls and bar counter area.
|
Electrical Rough-In | 3/23/2015 | 3/23/2015 | 3/23/2015 | P | PASS |
Rex Boyles
|
|
|
key to space is hidden in step light in rock column across from front door. Phone #: ###-#### Inspection requested via web by John Edwards r/i underslab feeder relocation ok
|
Issue PAID IN FULL permit | | | 3/23/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/23/2015 | | DONE |
|
|
|
This permit was created on the web by John Edwards
|