Final | 7/21/2015 | 7/22/2015 | 7/22/2015 | A | PASS |
Rock A. Hudson
|
|
|
Code for house 7105 in case no one is there. Call Lloyd ###-#### for any questions Phone #: ###-#### Inspection requested via web by Jerry Moore Final ok
|
Final | 7/14/2015 | 7/15/2015 | 7/15/2015 | A | FAIL |
Rock A. Hudson
|
|
|
If the house is locked the code is 7105. call Lloyd at ###-#### for any questions Phone #: ###-#### Inspection requested via web by Jerry Moore BCC- Shall have access to all electrical in garage. 210.8- All receptacles in kitchen area serving counter top surfaces shall have GFCI protection. Pantry. 210.8 All receptacle outlets located with in 6' of sink shall have GFCI protection. 314.20- All boxes set back 1/4" or more in tile shall have an extension ring. 406.5(B)- Receptacles and boxes shall be secured and flush with finished surface. 422.30- Hood disconnecting means shall be accessible. Receptacle shall not be located behind fixed panel.
|
Rough-In Permanent Service | 3/23/2015 | 3/24/2015 | 3/24/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Jerry Moore rough in ok cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 3/23/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/23/2015 | | DONE |
|
|
|
This permit was created on the web by Jerry Moore
|