Temporary Service | 4/13/2015 | 4/13/2015 | 4/13/2015 | P | PASS |
Rex Boyles
|
|
|
Lock box combo 4320, if you have any questions, please call Jake. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan corrections made t/s u/g rec ok
|
Temporary Service | 4/9/2015 | 4/10/2015 | 4/10/2015 | A | FAIL |
Daryl DeGrange
|
|
|
Lock box combo 4320, if you have any questions, please call Jake. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan NEC 250.92(B) Shall bond metal raceways with unfused conductors and concentric knockouts, between meterbase and disconnect
|
Conference | 4/3/2015 | 4/6/2015 | 4/6/2015 | A | DONE |
Rex Boyles
|
|
|
Please call Clay to meet you. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan discuss fire job. OK to reuse existing service disconnect and install new loadcenter to get power going for construction. Verify grounding electrode system for temp. service.
|
Issue PAID IN FULL permit | | | 4/3/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/3/2015 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|