Final | 9/18/2015 | 9/18/2015 | 9/18/2015 | P | PASS |
Eric Story
|
|
|
Shawn Phone #: ###-#### final ok
|
Final | 9/16/2015 | 9/17/2015 | 9/17/2015 | P | FAIL |
Eric Story
|
|
|
Call 30 mins before to meet // Shawn Phone #: ###-#### 406.4 (6) exterior receptacles shall be weather resistant type 406.12 all receptacles shall be tamper resistant 440.12 (d) disconnect required for a/c unit
|
Final | 8/26/2015 | 8/27/2015 | 8/27/2015 | A | CANC |
Eric Story
|
|
|
would like call ahead; Shawn Phone #: ###-#### needed p/s
|
Permanent Service | 8/27/2015 | 8/27/2015 | 8/27/2015 | P | PASS |
Eric Story
|
|
|
would like call ahead; Shawn Phone #: ###-#### p/s u/g n ok
|
Electrical Rough-In | 7/16/2015 | 7/16/2015 | 7/16/2015 | P | PASS |
Eric Story
|
|
|
Shawn Phone #: ###-#### rough-in ok cover
|
Electrical Rough-In | 7/15/2015 | 7/15/2015 | 7/15/2015 | P | NR |
Eric Story
|
|
|
Shawn Phone #: ###-#### homeowner not ready
|
Conference | 7/9/2015 | 7/10/2015 | 7/10/2015 | A | DONE |
Eric Story
|
|
|
Please call ahead for access - Shawn Phone #: ###-#### confrence with homeowner on recep locations and required circuits
|
Electrical Rough-In | 7/10/2015 | 7/10/2015 | 7/10/2015 | P | PASS |
Eric Story
|
|
|
Please call ahead for access - Shawn Phone #: ###-#### rough-in soffit cans ok cover
|
Application received | | | 4/7/2015 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 4/7/2015 | | DONE |
|
|
|
|