Final | 9/30/2015 | 9/30/2015 | 9/30/2015 | A | PASS |
Eric Story
|
|
|
John is available and should be on site Phone #: ###-#### Inspection requested via web by John Harvey final ok
|
Final | 9/29/2015 | 9/29/2015 | 9/29/2015 | P | FAIL |
Eric Story
|
|
|
Call Tim if any issues
Thank you Phone #: ###-#### Inspection requested via web by John Harvey 110.12 (a) all unused openings shall be closed 2" opening in panel 210.12 arc fault protection required for bedroom and smokes not GFCI protection
|
Final | 9/28/2015 | 9/28/2015 | 9/28/2015 | P | FAIL |
Eric Story
|
|
|
House is open. John is out of town Phone #: ###-#### Inspection requested via web by John Harvey 210.52(c) (1) a receptacle shall installed at each counter top space wider than 12" 210.12 arc fault protection required for bedrooms including smoke detectors 422.31 permanently installed appliances shall have a means of lockout Oven,micro,hood,dishwasher/downstairs living room in-op upstairs receptacles in built in cabinet need extended exterior receptacle not finished
|
Electrical Rough-In | 7/6/2015 | 7/7/2015 | 7/7/2015 | A | PASS |
Eric Story
|
|
|
Main level master floor heat only
John is out of town. The general contractor is available if any problems and will call john Phone #: ###-#### Inspection requested via web by John Harvey master bath floor heat ok cover
|
Electrical Rough-In | 6/22/2015 | 6/22/2015 | 6/22/2015 | P | PASS |
Eric Story
|
|
|
Garage rough in only.
John is currently out of town. Call Tim if any problems. Thank you much. Phone #: ###-#### Inspection requested via web by John Harvey rough-in detached garage ok cover
|
Rough-In Permanent Service | 5/13/2015 | 5/13/2015 | 5/13/2015 | P | PASS |
Daryl DeGrange
|
|
|
James is on site. Inspect meter panel so we can swing temp service to permanent.
Thank you Phone #: ###-#### Inspection requested via web by John Harvey p/s o/h rec ok
|
Electrical Rough-In | 4/15/2015 | 4/16/2015 | 4/16/2015 | P | PASS |
Daryl DeGrange
|
|
|
Call john if any issues. Gate code to get into property is 1403 Phone #: ###-#### Inspection requested via web by John Harvey rough-in ok cover
|
Temporary Service | 4/9/2015 | 4/9/2015 | 4/9/2015 | P | CANC |
Rock A. Hudson
|
|
|
John is out of town until later today. Call Tim if any issues. This inspection is only for trench inspection. Excavator is on site and is currently digging nearby sewer. Electrical conduit has been installed and photos have been taken Phone #: ###-#### Inspection requested via web by John Harvey Needed rough in inspection
|
Electrical Rough-In | 4/9/2015 | 4/9/2015 | 4/9/2015 | P | PASS |
Rock A. Hudson
|
|
|
John is out of town until later today. Call Tim if any issues. This inspection is only for trench inspection. Excavator is on site and is currently digging nearby sewer. Electrical conduit has been installed and photos have been taken Phone #: ###-#### Inspection requested via web by John Harvey 2" service lateral and 1 1/4" feeder to garage rough in ok cover
|
Issue PAID IN FULL permit | | | 4/9/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/9/2015 | | DONE |
|
|
|
This permit was created on the web by John Harvey
|