Final | 7/8/2015 | 7/8/2015 | 7/8/2015 | P | PASS |
Rock A. Hudson
|
|
|
CODE 4224 READY AM Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
Rough-In Permanent Service | 4/23/2015 | 4/24/2015 | 4/24/2015 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
|
Issue PAID IN FULL permit | | | 4/17/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/17/2015 | | DONE |
|
|
|
This permit was created on the web by Bob Glenn
|