First Notice | 5/22/2015 | 5/22/2015 | 1/15/2018 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by David Mackey
|
Final | 5/21/2015 | 5/22/2015 | 5/22/2015 | A | PASS |
Rock A. Hudson
|
|
|
Corrections have been made. Please final Phone #: ###-#### Inspection requested via web by David Mackey final ok
|
Permanent Service | 5/19/2015 | 5/19/2015 | 5/19/2015 | P | PASS |
Rock A. Hudson
|
|
|
This is a billboard structure located on the north side of Franklin RD just West of Cloverdale. Meter was removed with anticipation of removing billboard sign. Plans changed and the sign will stay in place. We extended the weather-head away from the catwalk and installed new service wire. Phone #: ###-#### Inspection requested via web by David Mackey p/s o/h rec ok
|
Final | 5/19/2015 | 5/19/2015 | 5/19/2015 | P | FAIL |
Rock A. Hudson
|
|
|
This is a billboard structure located on the north side of Franklin RD just West of Cloverdale. Meter was removed with anticipation of removing billboard sign. Plans changed and the sign will stay in place. We extended the weather-head away from the catwalk and installed new service wire. Phone #: ###-#### Inspection requested via web by David Mackey as per 408.41 grounded conductor in a panelboard shall have individual terminal that is not also used for another conductor
|
Issue PAID IN FULL permit | | | 4/28/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/28/2015 | | DONE |
|
|
|
This permit was created on the web by David Mackey
|