Final | 7/14/2015 | 7/14/2015 | 7/14/2015 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn ok final
|
Rough-In Permanent Service | 5/4/2015 | 5/4/2015 | 5/4/2015 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn ri ok, p/s u/g n ok
|
Final | 5/4/2015 | 5/4/2015 | 5/4/2015 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Inspection cancelled from web by: Darryn Coburn
|
Issue PAID IN FULL permit | | | 4/30/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/30/2015 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|