First Notice | 5/4/2015 | 5/4/2015 | 5/18/2015 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Krista Ratterree
|
Final | 5/4/2015 | 5/4/2015 | 5/4/2015 | P | PASS |
Rock A. Hudson
|
|
|
Dustin is finished up the issues with the cabinet you requested Friday. Thank you very much for putting up with us during this site!!!! Phone #: ###-#### Inspection requested via web by Krista Ratterree Final ok
|
Final | 5/1/2015 | 5/1/2015 | 5/1/2015 | P | CANC |
Rock A. Hudson
|
|
|
###-#### I created no call back
|
Final | 5/1/2015 | 5/1/2015 | 5/1/2015 | P | FAIL |
Rock A. Hudson
|
|
|
As early as possible would be great! Thank you..... Phone #: ###-#### Inspection requested via web by Krista Ratterree 310.15(B)(16)- #10 THHN protected by 100 amp breaker 30 amp max. #8 THHN protected by 60 amp breaker 50 amp max. 408.30(D)- Back fed over curent device shall be secured in place by additional fastener.
|
Rough-In Permanent Service | 4/30/2015 | 4/30/2015 | 4/30/2015 | P | PASS |
Rock A. Hudson
|
|
|
This inspection only for open trench so they can cover, equipment wiring will be separate inspection.
Thank you, Phone #: ###-#### Inspection requested via web by Krista Ratterree Conduit has seperated that feeds service, asked contractor to schedule repair. No service inspection at this time just underground. Underground from service around front to white cabinet on northside rough in ok cover
|
Issue PAID IN FULL permit | | | 4/30/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 4/30/2015 | | |
|
|
|
|
Application received | | | 4/30/2015 | | DONE |
|
|
|
This permit was created on the web by Krista Ratterree
|